When can Tandem Circuit Breakers be Used

May 25, 2017 Common Questions Information for Buyers and Sellers 0

There’s lots of confusion on this topic…Maybe the following will help.  Thanks to Reuben Saltzman, Home Inspector in the Minneapolis Metro Area.

Many Different Types of Breakers

Confusion abounds over the use of tandem circuit breakers in panelboards, even among electricians and electrical inspectors.  Today I’ll set  the record straight as to when tandem circuit breakers can be used.   This is an adaptation of an article I wrote for the ASHI Reporter, which was published in February of 2011.

First, a quick definition.  A tandem circuit breaker is a double circuit breaker that takes up the space of a single circuit breaker on a panelboard. You’ll also hear them called duplex, slimline, twin, half-height, half-inch, double and wafer breakers, depending on local customs. While a two-pole circuit breaker gets connected to two different poles at a panelboard and has a common trip or a handle tie for simultaneous disconnecting of two poles, a tandem breaker does not.

Because tandem circuit breakers allow for two circuits to be installed on a panelboard in a one circuit breaker space, they’re typically used after a panelboard has been filled to capacity with standard circuit breakers. Because of this, they’re often referred to as “cheaters.”

Is this really ‘cheating’? No, it’s not. The use of tandem circuit breakers is a perfectly acceptable practice, as long as the panelboard is designed for tandem circuit breakers and they’re installed in locations within the panelboard where they’re allowed.

How does a home inspector determine whether tandem circuit breakers are allowed on the panelboard they’re inspecting? There are a number of ways to do so.

Class CTL Panelboards

Panelboards must follow UL  Standard 67, which requires all lighting and appliance panelboards to be Class CTL (Circuit Total Limiting). Here’s an old formula for determining how many circuits are allowed in the Class CTL panelboard being inspected; this formula is helpful to use when inspecting older electric panels without clear labeling inside the panel. Take the amperage of the panelboard, multiply by the number of poles, and divide by 10. It sounds complicated, but it’s not — let’s use a 100-amp panelboard as an example:

100 Amp x 2 Poles = 200 200 / 10 = 20

Based on this formula, the maximum number of circuits allowed in a 100-amp 120/240-volt panelboard is 20. For panelboards not manufactured as “lighting & appliance” panelboards, there is no limit to the number of circuit breakers allowed.  This formula is also no longer applicable for today’s panels.

The 2008 National Electrical Code (NEC) makes it a little confusing.  Previous editions of the NEC limited the maximum number of circuits in a lighting and appliance panelboard to 42.  The 2008 version of the NEC removed the “lighting & appliance” panelboard designation, however, NEC 408.54 says “A panelboard shall be provided with physical means to prevent the installation of more overcurrent devices than that number for which the panelboard was designed, rated, and listed.”

Manufacturers still list the maximum number of circuit breakers allowed, and must provide a rejection feature to help prevent the use of tandem circuit breakers where not allowed.

Class CTL panelboards have different methods of preventing class CTL tandem circuit breakers from being used in locations where they’re not allowed.  This is referred to as a “rejection feature”.  In the photo below, the highlighted bus stabs are notched to allow the use of tandem circuit breakers; the bus stabs which don’t have this notch won’t allow tandem breakers.

Does the panelboard allow tandems?

Now that I’ve talked about the general rules for tandem circuit breakers, I’ll discuss the ways that home inspectors or electrical inspectors can determine when tandem circuit breakers are allowed in various panelboards.

The model of the panelboard

The model or part number of the electric panelboard usually will indicate whether or not the electric panelboard is designed to accept tandem breakers and how many can be used. Here are a few examples:

  • G3040BL1200 = 30 spaces, 40 total circuits allowed. Up to 10 tandem circuit breakers can be used.
  • G3030BL1150 = 30 spaces, 30 total circuits allowed. Tandem circuit breakers are not allowed.
  • BR1220B100 = 12 spaces, 20 total circuits allowed. Up to 8 tandem circuit breakers can be used.
  • BR1212B100 = 12 spaces, 12 total circuits allowed. Tandem circuit breakers are not allowed.
  • HOMC20U100C = 20 spaces, 20 total circuits allowed. Tandem circuit breakers are not allowed.

I think it’s easy enough to see the pattern.

What’s the concern with tandem circuit breakers?

When tandem circuit breakers are used in locations where they’re not allowed, they could make an improper physical connection to the bus bar in the panelboard, which can create a fire hazard. Tandem circuit breakers also increase the total load on the bus bars in a panelboard; this is where home inspectors need to use common sense.

When a home inspector finds tandem circuit breakers used in improper locations, they’ll often recommend repair by an electrician. If the bus bars of the panelboard have been damaged or altered to allow for the installation of tandem circuit breakers, the proper repair is to have the panelboard replaced. There is no way for a home inspector to determine if the bus bars have been damaged without actually removing the circuit breakers, which is something home inspectors shouldn’t be doing.

 